Q:
Why doesn't my MS-9050UD find all of its "devices" during Auto-Program?
A:
Please make sure that they no devices are addressed over 50. The MS-9050UD supports 50 devices addressed from 1 to 50.
MS-9200UDLS / MS-5UD / MS-10UD:
Q: What's does the message: Trouble In System Remote Sync Fault on the panel mean?
A: The Remote Power Supply Sync output TB2 requires a 4.7K ohm resistor for proper supervision.
MS-9200UD / MS-9200UDLS / MS-9600:
Q: Will a LCD-40 work on an MS9200UD/UDLS - MS-9600?
A: No. The LCD-40 can only annunciate 40 characters. The MS9200UD/UDLS has 80 characters.
MS-9200UD (LS) / MS-9600:
Q: How many conductors are required when installing the LCD-80F?
A: 6
MS-9200UD / MS-9200UDLS / MS-9600:
Q: Since the ACS series annunciators use a different communication bus than the LCD-80, can I employ both at the same time?
A: Yes.
MS-9200UDLS:
Q: Why is my central station getting the wrong point device report for my modules and pull stations and I'm sending CID?
A: See page 114 of your manual. The UDLS reports modules and pulls stations with a 159 point shift. This means whatever address point (barring detectors) reports, you will need to add 159 to the address itself. (Pull station address 10 is activated, central station will get a 169 reported).
ACC-25/50 (ZS):
Q: I have an ACC-25/50 that is showing a system trouble. How can I clear this trouble?
A: Make sure on the main board that the 4.7K ohm EOL resister is on the Master CMD Output, and CMD2, CMD3, CMD4, or CMD5 Inputs.
ACC-25/50:
Q: Can I install a ZPMK or an ACC-ZSM on my ACC25/50?
A: No. These modules can only be replaced on an ACC25/50ZS. The ACC25/50 cannot support these modules
All Dialers:
Q: Does the dialer require 2 phones lines?
A: Yes, or the panel will always have a phone line 2 trouble.
PK-Plus:
Q: Can I run PK-PLUS in Microsoft Windows Vista?
A: To use PK-PLUS in Microsoft Windows Vista, PK-PLUS will have to run in Windows XP Compatibility mode. Please see Microsoft.com for further information about Windows XP Compatibility mode.
Beam Detectors:
Q: Why is my new installed beam detector coming up on the FACP display as "Dirty 1"?
A: As the beam detector was being manually aligned the chamber values were being calculated and changing with the changes being made to it. As a result, the chamber value(s) are now out of tolerance. To correct this, change the beam detector's address to a new unused address, delete the old address of the beam detector, and then do an auto-program.